Jon W

Jon W Job Checkin

Conducted warranty inspection of in-floor heating system installed in March. Documented structural issues including significant concrete cracking and pipe damage in the recreation room. Multiple photos taken showing vertical fractures in the concrete with visible moisture damage and discoloration around affected areas. Scheduled service advisor for further assessment.

Conducted warranty inspection of in-floor heating system installed in March. Documented structural issues including significant concrete cracking and pipe damage in the recreation room. Multiple photos taken showing vertical fractures in the concrete with visible moisture damage and discoloration around affected areas. Scheduled service advisor for further assessment. Conducted warranty inspection of in-floor heating system installed in March. Documented structural issues including significant concrete cracking and pipe damage in the recreation room. Multiple photos taken showing vertical fractures in the concrete with visible moisture damage and discoloration around affected areas. Scheduled service advisor for further assessment.

Roger M.

Roger M. Job Checkin

Responded to no heat call for 20-year-old Bryant natural gas furnace exhibiting short cycling and error code 13. Inspection revealed a suspected cracked heat exchanger, confirmed through visual assessment of the interior components. Reset system temporarily restored operation, but recommended replacement due to age and safety concerns.

Responded to no heat call for 20-year-old Bryant natural gas furnace exhibiting short cycling and error code 13. Inspection revealed a suspected cracked heat exchanger, confirmed through visual assessment of the interior components. Reset system temporarily restored operation, but recommended replacement due to age and safety concerns. Responded to no heat call for 20-year-old Bryant natural gas furnace exhibiting short cycling and error code 13. Inspection revealed a suspected cracked heat exchanger, confirmed through visual assessment of the interior components. Reset system temporarily restored operation, but recommended replacement due to age and safety concerns.

Koshoua V.

Koshoua V. Job Checkin

Performed annual furnace tune-up maintenance per service agreement. Discovered condensate trap filled with debris and dirty water causing blockage; cleared and thoroughly blew out the system. Completed preventative maintenance including flame sensor cleaning, air filter inspection, gas pressure verification, carbon monoxide check, and removal of spiderweb accumulation from unit. Control board inspection revealed proper connections and functioning electronic components.

Performed annual furnace tune-up maintenance per service agreement. Discovered condensate trap filled with debris and dirty water causing blockage; cleared and thoroughly blew out the system. Completed preventative maintenance including flame sensor cleaning, air filter inspection, gas pressure verification, carbon monoxide check, and removal of spiderweb accumulation from unit. Control board inspection revealed proper connections and functioning electronic components. Performed annual furnace tune-up maintenance per service agreement. Discovered condensate trap filled with debris and dirty water causing blockage; cleared and thoroughly blew out the system. Completed preventative maintenance including flame sensor cleaning, air filter inspection, gas pressure verification, carbon monoxide check, and removal of spiderweb accumulation from unit. Control board inspection revealed proper connections and functioning electronic components.

Koshoua V.

Koshoua V. Job Checkin

Performed routine furnace maintenance on 9-10 year old Tempstar unit. Found significant rust and debris buildup in condensation trap and drain line; cleared blockage to restore proper drainage. Conducted combustion analysis, checked/adjusted gas pressures to manufacturer specifications, and verified carbon monoxide levels within safe parameters.

Performed routine furnace maintenance on 9-10 year old Tempstar unit. Found significant rust and debris buildup in condensation trap and drain line; cleared blockage to restore proper drainage. Conducted combustion analysis, checked/adjusted gas pressures to manufacturer specifications, and verified carbon monoxide levels within safe parameters. Performed routine furnace maintenance on 9-10 year old Tempstar unit. Found significant rust and debris buildup in condensation trap and drain line; cleared blockage to restore proper drainage. Conducted combustion analysis, checked/adjusted gas pressures to manufacturer specifications, and verified carbon monoxide levels within safe parameters.